Skip to main content

HIERSUN POWER GENSET LOAD TEST PROCEDURES

HIERSUN POWER GENSET LOAD TEST PROCEDURES


GENSET

A common base frame skid mounted genset comes with radiator cooled diesel engine coupled to industrial brushless alternator.

1.   OBJETIVES

1.1.      To ensure that the diesel engine is operating satisfactorily without undue vibration and overheating.
1.2.      To ensure that the diesel engine is able to sustain prolong running on full load without any sign of straining and abnormalities.
1.3.      To ensure that the safety shutdown devices are operative.
1.4.      To check on any other operating characteristic (not standard) if required by the client.
1.5.      To verify the fuel consumption against specification data of diesel engine.

2.   MEASURING AND RECORDING INSTRUMENT

All electrical recording such as voltmeters, ammeters, frequency meters, hour run meters, factor meters including volts, amperes and frequency are installed in the control panel in the control room.

3.   DUMMY LOADS

The diesel engine is coupled to an alternator and the power supply terminals are connected to dummy loads by either one or combination or both of the two special designed industrial ‘grid type’ resistance banks.

4.    TEST PROCEDURE

The Load Test consists of three stages:

4.1   No load To Full Load Test- Using Dummy Loads

The generating set is started up with no load gradually Increased with resistive loads in steps to Full Load.
                 To duration for standard test is as follow:-
                 Dummy load            Testing Time
                 No Load                   5 minutes
                 25% full load current          15 minutes
                 50% full load current          15 minutes
                 75% full load current          30 minutes
                 100% full load current       60 minutes
                 110% full load current       60 minutes

                                  TOTAL    3 hours

           4.2     Safety Devices Shutdown Test

4.2.1           Low engine oil pressure fault is simulated by short circuiting its sensing device to earth which would signal the emergency relay to shutdown the engine.
4.2.2          Similarly, when the high water temperature fault is simulated, the engine should down automatically.
4.2.3           The engine speed is adjusted to run above 1500 rpm and when it exceeds 15% of the rated speed, the speed governor switch should signal the emergency relay to shutdown the engine.







5.    TEST RECORD AND REPORT 

Before commencement of load test, all relevant information for the diesel engine is entered into standard ‘Test Report Sheet’ (please refer to sample attached). The test results obtained during the various stage of the test are recorded in the standard format.


 6.     CRITERIA OF TEST MEASUREMENT

6.1    Fuel consumption reading for respective loads will be recorded.
6.2    The engine speed in (RPM) is read off from the engine tachometer.
6.3    Cooling water temperature (in 0C) is taken at the engine water outlet pipe using the engine tachometer.
6.4    Lube oil pressures (in psi) is read from engine pressure gauge.
     



Comments

Popular posts from this blog

China genuine Cummins generator part II (Stamford identification)

 For Choosing  genuine engines such as cummins, perkins, MTU and volve power for the generator, a same level alternator such as Stamford, Marathon will be the best choice.  Earlier we talk about how to identify Cummins engine for the China Cummins genset , and  it is time for us heading for discuss the STAMFORD alternator. However, have you heard millions rumors of the fake Stamford alternator produced in China? Unfortunately,most of be said is ture.  Copy, fake, cheap stamford alternator are occupying some percentage market share in somewhere. So how to identify the genuine ones is coming up to the subject. Today, we would like to show non-technical part checking. And please note that our documents published below are  the most updated ones from Stamford newage in China now. Not for the ones you bought before 06/2013. Latest name plate of cummins generatortechnologies newage  ( Self-adhesive paper) This is very important, from late 2013 , genuine newage St

Japan Mitsubishi 6D34T brand new engine Hiersun Power | Industrial Engin...

Japan Mitsubishi 6D34T brand new engine Hiersun Power | Industrial Engine Stockist

403d-07 Perkins surplus new engine |Hiersun Power | unused madein Japan ...

Perkins 403D-07 new surplus new engine GH built list Hiersun Power| Huge stock of Perkins engines